BS EN 12101-13:2022
$215.11
Smoke and heat control systems – Pressure differential systems (PDS). Design and calculation methods, installation, acceptance testing, routine testing and maintenance
Published By | Publication Date | Number of Pages |
BSI | 2022 | 126 |
This document gives calculation methods, guidance and requirements for the design, installation, acceptance testing, routine testing and maintenance for pressure differential systems (PDS). PDSs are designed to hold back smoke at a leaky physical barrier in a building, such as a door (either open or closed) or other similarly restricted openings and to keep tenable conditions in escape and access routes depending on the application. It covers systems intended to protect means of escape e.g. staircases, corridors, lobbies, as well as systems intended to provide a protected firefighting space (bridgehead) for the fire services. It provides details on the critical features and relevant procedures for the installation. It describes the commissioning procedures and acceptance testing criteria required to confirm that the calculated design is achieved in the building. This document gives rules, requirements and procedures to design PDS for buildings up to 60 m. For buildings taller than 60 m the same requirements are given (e.g. Table 1), but additional methods of calculation and verification are necessary. Requirements for such methods and verification are given in Annex D, but the methods fall outside the scope of this document [e.g. Additional mathematical analysis and/or Computational Fluid Dynamics (CFD)]. Routine testing and maintenance requirements are also defined in this document. In the absence of national requirements and under expected ambient and outside conditions, the requirements in Table 1 are fulfilled by the PDS.
PDF Catalog
PDF Pages | PDF Title |
---|---|
2 | undefined |
10 | 1 Scope 2 Normative references |
11 | 3 Terms and definitions |
12 | 4 Design objectives |
13 | 5 Requirements |
17 | 5.5.2.1 General 5.5.2.2 Pressurization systems with passive air release |
18 | 5.5.2.3 Pressurization systems with active air release 5.6.2.1 Connected lobbies |
19 | 5.6.2.2 Connected corridors 5.6.3.1 General |
20 | 5.6.3.2 Example 1: Staircase protection (pressurization system) |
21 | 5.6.3.3 Example 2: Staircase, firefighters lift, and/or other lift shaft(s), protection (pressurization system) |
22 | 5.6.3.4 Example 3: Staircase protection (pressurization system) |
23 | 5.6.3.5 Example 4: Staircase, firefighters lift and/or other lift shaft(s), protection (pressurization system) |
24 | 5.6.3.6 Example 5: Staircase protection (pressurization system) |
25 | 5.6.3.7 Example 6: Staircase protection (pressurization system) |
26 | 5.6.3.8 Example 7: Staircase, firefighters lift and/or other lift shaft(s), protection (pressurization system) |
27 | 5.6.3.9 Example 8: Staircase and lobby protection (pressurization system) |
28 | 5.6.3.10 Example 9: Staircase, lobby and firefighters lift shaft protection (pressurization system) |
30 | 5.6.6.1 General 5.6.6.2 Air intake |
31 | 5.6.6.3 Air supply to firefighter lift and other lift shafts 5.6.6.4 Air supply to staircases 5.6.7.1 General |
32 | 5.6.7.2 Passive air release by openings in the façade 5.6.7.3 Passive air release by shafts and/or duct systems 5.6.7.4 Active air release by shafts and/or duct systems |
33 | 6 Interaction |
35 | 7 Equipment and components – specification and installation |
47 | 8 Testing and measuring |
57 | 8.5.5.1 General 8.5.5.2 Fire detection system 8.5.5.3 Smoke detectors as an integrated part of the PDS 8.5.5.4 Manual control of PDS for firefighters |
58 | 8.5.5.5 Manual activation for means of escape (operated by escaping people) 9 Additional considerations for design and testing |
59 | 10 Documentation |
61 | 11 Testing and Maintenance, design changes, faults, routine testing and operation |
63 | 11.5.2.1 General 11.5.2.2 Daily testing 11.5.2.3 Monthly testing |
64 | 11.5.2.4 Yearly testing |
65 | 11.5.2.5 Auto test and communication technology |
66 | Annex A (informative)Calculation procedures A.1 General |
67 | A.2 Calculation procedure |
68 | A.3 Basic rules A.3.1 Calculation of volume flowrates through openings (QOPENING) |
69 | A.3.2 Air velocities through geometric openings A.3.3 Leakage paths A.3.3.1 General A.3.3.2 Parallel leakage paths, Aep |
70 | A.3.3.3 Series leakage paths, Aes A.4 Estimation of door closed volume supply rate A.4.1 Estimation of leakage rate through closed doors A.4.1.1 Air leakage data for closed doors |
72 | A.4.1.2 Estimation of leakage through closed doors (QDC) A.4.1.3 Estimation of leakage through lift landing doors (QLD) |
73 | A.4.2 Estimation of leakage rate via closed windows A.4.2.1 Air leakage data for windows A.4.2.2 Estimation of leakage via closed windows (QWC) |
74 | A.4.3 Estimation of leakage rates through walls A.4.3.1 Air leakage data for walls A.4.3.2 Estimation of leakage through walls (QWALL) |
75 | A.4.4 Estimation of leakage rate through floors A.4.4.1 Air leakage data for floors A.4.4.2 Estimation of leakage through floors (QFLOOR) A.4.5 Estimation of total leakage rate with doors closed (QSDC) A.4.6 Estimation of other leakages (QDCOT), and final exit door leakage (QED) |
76 | A.4.7 Estimate flushing volume (QFLUSH) A.4.8 Estimation of system supply rate with doors closed (QTDC) A.5 Estimation of door open airflows A.5.1 Estimation of protected space door open volume flowrate through the door between the protected and unprotected space (QDO) |
77 | A.5.2 Estimation of passive air release paths A.5.2.1 General A.5.2.2 Estimation of recommended minimum vent area requirements (AVA) |
78 | A.5.2.3 Estimation of the recommended size of air release shafts (AVS) A.5.3 Estimation of the pressure in the unprotected space (PUS) |
79 | A.5.4 Estimation of the pressure in the staircase (PSC) A.5.5 Estimation of the pressure in the unprotected space (PUS) for active air release A.5.6 Estimation of the exit door flowrate (QEDO), where required by the design concept |
80 | A.5.7 Estimation of the flowrate with the door open (QTDO) A.6 Finalize design A.6.1 Estimate design flowrate (QDESIGN) A.6.2 Determine fan supply path A.6.2.1 General A.6.2.2 Estimation of mechanical extract requirements |
81 | A.6.3 Estimation of the pressure drop across the staircase |
82 | A.6.4 Pressure distribution across the staircase A.6.4.1 General |
83 | A.6.4.2 Estimation of door opening forces; Maximum pressure across doors A.6.4.3 Door opening force limitations; Maximum pressure in the staircase. |
84 | A.6.5 Estimate relief vent area (APV) A.7 Other considerations |
85 | Annex B (informative)Design example and possible calculation procedures B.1 General |
86 | B.2 Pressurization calculation |
95 | Annex C (informative)Further information on wind and temperature effects C.1 General C.2 Influence of wind effect C.3 Pressure in the protected space |
96 | C.4 Natural air release (Passive air release) C.5 Powered air release (Active air release) C.6 Influence of temperature effect |
97 | C.7 Pressure control C.7.1 Passive pressure control C.7.2 Active pressure control C.8 Assessment of meteorological effect during performance test C.8.1 General C.8.2 Wind effect C.8.3 Stack effect |
98 | Annex D (informative)Guidance for PDS design for buildings taller than 60 m D.1 General D.2 Principles |
99 | D.3 Requirements D.4 Selection of the engineering method D.4.1 General |
100 | D.4.2 Multizone airflow models (zone-knot-models) D.4.3 Computational Fluid Dynamics (CFD) D.5 Climatic input data D.6 Information required for simulations D.6.1 General |
101 | D.6.2 Content requirements |
102 | D.6.3 Presentation of the results D.7 Project assessment by authorities having jurisdiction |
103 | Annex E (informative)Example of firefighters’ intervention in building equipped with PDS |
104 | Annex F (informative)Documentation and responsibilities in the process F.1 General F.2 Concept studies |
105 | F.3 Planning and Engineering F.4 Execution stage F.5 Occupation phase |
107 | Annex G (informative)(Example) PDS concept report |
110 | Annex H (informative)(Example) PDS test report |
118 | Annex I (informative)Risk assessment – List of potential disturbances |
120 | Annex J (informative)Practical suggestions for successful commissioning |
121 | Annex K (normative)Labelling — Information and position |