Shopping Cart

No products in the cart.

BS EN 61643-11:2012+A11:2018

$215.11

Low-voltage surge protective devices – Surge protective devices connected to low-voltage power systems. Requirements and test methods

Published By Publication Date Number of Pages
BSI 2018 118
Guaranteed Safe Checkout
Categories: ,

If you have any questions, feel free to reach out to our online customer service team by clicking on the bottom right corner. We’re here to assist you 24/7.
Email:[email protected]

This part of IEC 61643 is applicable to devices for surge protection against indirect and direct effects of lightning or other transient overvoltages. These devices are packaged to be connected to 50/60 Hz a.c. power circuits, and equipment rated up to 1 000 V r.m.s. Performance characteristics, standard methods for testing and ratings are established. These devices contain at least one nonlinear component and are intended to limit surge voltages and divert surge currents.

PDF Catalog

PDF Pages PDF Title
2 undefined
21 English

CONTENTS
26 FOREWORD
28 INTRODUCTION
29 1 Scope
2 Normative references
3 Terms, definitions and abbreviations
30 3.1 Terms and definitions
35 3.2 Abbreviations
36 Tables

Table 1 – List of Abbreviations
37 4 Service conditions
4.1 Frequency
4.2 Voltage
4.3 Air pressure and altitude
4.4 Temperatures
4.5 Humidity
5 Classification
5.1 Number of ports
5.2 SPD design
5.3 Class I, II and III tests
38 5.4 Location
5.5 Accessibility
5.6 Mounting method
5.7 Disconnectors (including overcurrent protection)
5.8 Degree of protection provided by enclosures
Table 2 – Class I, II and III tests
39 5.9 Temperature and humidity range
5.10 Power system
5.11 Multipole SPD
5.12 SPD failure behaviour
6 Preferred values for SPD
6.1 Preferred values of impulse discharge current Iimp for class I tests
6.2 Preferred values of nominal discharge current for class II tests In
6.3 Preferred values of open-circuit voltage for class III tests Uoc
6.4 Preferred values of voltage protection level Up
6.5 Preferred values of r.m.s. maximum continuous operating voltage Uc
40 7 Requirements
7.1 General requirements
41 7.2 Electrical requirements
44 7.3 Mechanical requirements
46 7.4 Environmental and material requirements
47 7.5 Additional requirements for specific SPD designs
48 7.6 Additional requirements as may be declared by the manufacturer
8 Type tests
49 8.1 General testing procedures
50 Figures

Figure 1 – Metallic screen test set-up
51 Table 3 – Type test requirements for SPDs
53 Table 4 – Common pass criteria for type tests
54 Table 5 – Cross reference for pass criteria versus type tests
55 Table 6 – Preferred parameters for class I test
58 Figure 2 – Example of a decoupling network for single-phase power
Figure 3 – Example of a decoupling network for three-phase power
Figure 4 – Alternate test for the measured limiting voltage
59 8.2 Indelibility of markings
8.3 Electrical tests
61 Figure 5 – Flow chart of testing to check the voltage protection level Up
62 Table 7 – Tests to be performed to determine themeasured limiting voltage
64 Figure 6 – Flow chart of the operating duty test
65 Figure 7 – Test set-up for operating duty test
66 Figure 8 – Operating duty test timing diagram for test classes I and II
67 Figure 9 – Additional duty test timing diagram for test class I
Figure 10 – Operating duty test timing diagram for test class III
69 Table 8 – Prospective short-circuit current and power factor
71 Figure 11 – Test circuit for SPD with Ifi lower than the declared short-circuit rating
72 Figure 12 – Test circuit for SPD’s failure mode simulation
Figure 13 – Timing diagram for SPD’s failure mode simulation
74 Table 9 – Dielectric withstand
76 Figure 14 – Example of a test circuit to perform the test under TOVs caused by faults in the low voltage system
Figure 15 – Timing diagram for the test under TOVs caused by faults
in the low voltage system
78 Figure 16 – Example of circuit for testing SPDs for use in TT systems under TOVs caused by faults in high (medium) voltage systems
79 8.4 Mechanical tests
Figure 17 – Timing diagram for use in testing SPDs under TOVs caused by faults in the high (medium) voltage system using circuit of Figure 16
80 Table 10 – Screw thread diameters and applied torques
81 Table 11 – Cross-sections of copper conductors forscrew-type or screwless terminals
82 Table 12 – Pulling forces (screw terminals)
Table 13 – Conductor dimensions
83 Table 14 – Pulling forces (screwless terminals)
85 Table 15 – Air clearances for SPDs
86 Table 16 – Creepage distances for SPDs
87 Table 17 – Relationship between material groups and classifications
88 Figure 18 – Test apparatus for impact test
89 Figure 19 – Striking element of the pendulum hammer
90 Table 18 – Fall distances for impact requirements
91 8.5 Environmental and material tests
92 Figure 20 – Ball thrust tester
Figure 21 – Loading rod for ball thrust tester
94 8.6 Additional tests for specific SPD designs
Table 19 – Test conductors for rated load current test
95 Table 20 – Current factor k for overload behaviour
96 Figure 22 – Examples for appropriate test circuits of the load side short-circuit test(s)
97 8.7 Additional tests for specific performance if declared by the manufacturer
98 Table 21 – Tolerances for proportional surge currents
99 9 Routine and acceptance tests
9.1 Routine tests
9.2 Acceptance tests
100 Annex A (normative)
Reference test voltages for SPDs UREF
101 Table A.1 – Reference test voltage values
105 Annex B (normative)
TOV Ratings
Table B.1 – TOV test values for systems complying with IEC 60364 series
106 Table B.2 – TOV test parameters for North American systems
107 Table B.3 – TOV test parameters for Japanese systems
108 Annex C (normative)
Tests to determine the presence of a switching component and the magnitude of the follow current
110 Annex D (normative)
Reduced test procedures
111 Table D.1 – Reduced test procedure for SPDs complying with IEC 61643-1:2005
112 Annex E (informative) Alternative circuits for testing SPDs under TOVs caused
by faults in the high (medium) voltage system
Figure E.1 – Examples of a three-phase and single-phase circuit for use in testing SPDs under TOVs caused by faults in the high (medium) voltage system
113 Annex F (informative)
Environmental tests for outdoor SPDs
115 Annex G (normative)
Temperature rise limits
Table G.1 – Temperature-rise limits
116 Bibliography
BS EN 61643-11:2012+A11:2018
$215.11