Shopping Cart

No products in the cart.

BS EN 62052-31:2016

$256.21

Electricity metering equipment (AC). General requirements, tests and test conditions – Product safety requirements and tests

Published By Publication Date Number of Pages
BSI 2016 204
Guaranteed Safe Checkout
Categories: ,

If you have any questions, feel free to reach out to our online customer service team by clicking on the bottom right corner. We’re here to assist you 24/7.
Email:[email protected]

This part of IEC 62052 specifies product safety requirements for equipment for electrical energy measurement and control.

NOTE 1 For other requirements, see the relevant standards.

This International Standard applies to newly manufactured metering equipment designed to measure and control electrical energy on 50 Hz or 60 Hz networks with a voltage up to 600 V, where all functional elements, including add-on modules are enclosed in or form a single case.

NOTE 2 The voltage mentioned above is the voltage line-to-neutral derived from nominal voltages. See Table 7.

This International Standard also applies to metering equipment containing supply and load control switches, but only those which are electromechanical in operation.

NOTE 3 For components and sub-assemblies, see Clause 13.

When such equipment is designed to be installed in a specified matching socket, then the requirements apply to, and the tests shall be performed on, equipment installed in its specified matching socket. However, requirements for sockets and inserting / removing the meters from the socket are outside the scope of this standard.

This International Standard is also applicable to auxiliary input and output circuits.

NOTE 4 Examples are impulse inputs and outputs, control inputs and outputs, circuits for meter data exchange.

In this standard distinction is made between:

  • electromechanical meters, static meters and equipment for tariff and load control;

  • direct connected, current transformer operated, voltage and current transformer operated meters;

  • protective class I and protective class II equipment;

  • wall or cabinet mounted, rack mounted and panel mounted equipment;

  • equipment intended for indoor use and outdoor use.

Equipment used in conjunction with equipment for electrical energy measurement and control may need to comply with additional safety requirements. See also Clause 13.

NOTE 5 Examples are telecommunication modems and customer information units.

This International Standard does not apply to:

  • equipment where the voltage line-to-neutral derived from nominal voltages exceeds 600 V;

  • portable meters;

NOTE 6 Portable meters are meters that are not permanently connected

  • laboratory and mobile meter test equipment;

  • reference standard meters.

The safety requirements of this standard are based on the following assumptions:

  • metering equipment has been installed correctly;

  • metering equipment is used generally by unskilled persons, including meter readers and consumers of electrical energy. In many cases, it is installed in a way that it is freely accessible. Its terminal covers cannot be removed and its case cannot be opened without removing seals and using a tool;

  • during normal use all terminal covers, covers and barriers providing protection against accessing hazardous live parts are in place;

  • for installation, configuration, maintenance and repair it may be necessary to remove terminal cover(s), (a part of) the case or barriers so that hazardous live parts may become accessible. Such activities are performed by skilled personnel, who have been suitably trained to be aware of working procedures necessary to ensure safety. Therefore, safety requirements covering these conditions are out of the Scope of this standard.

PDF Catalog

PDF Pages PDF Title
4 European foreword
Endorsement notice
7 Annex ZA (normative) Normative references to international publications with their corresponding European publications
10 CONTENTS
16 FOREWORD
18 INTRODUCTION
20 1 Scope and object
1.1 Scope
21 1.2 Object
1.2.1 Aspects included in scope
1.2.2 Aspects excluded from scope
22 1.3 Verification
1.4 Environmental conditions
1.4.1 Normal environmental conditions
1.4.2 Extended environmental conditions
23 1.4.3 Extreme environmental conditions
2 Normative references
24 3 Terms and definitions
3.1 Equipment and states of equipment
25 3.2 Parts and accessories
27 3.3 Quantities
29 3.4 Tests
3.5 Safety terms
33 3.6 Insulation
37 3.7 Terms related to switches of metering equipment
39 4 Tests
4.1 General
4.2 Type test – sequence of tests
40 4.3 Reference test conditions
4.3.1 Atmospheric conditions
4.3.2 State of the equipment
43 Tables
Table 1 – Test copper conductors for current and switch terminals
44 4.4 Testing in single fault condition
4.4.1 General
4.4.2 Application of fault conditions
46 4.4.3 Duration of tests
4.4.4 Conformity after application of fault conditions
47 5 Information and marking requirements
5.1 General
48 Table 2 – Information requirements
49 5.2 Labels, signs and signals
5.2.1 General
50 Table 3 – IEC 60417 symbols and ISO 7000 that may be used on metering equipment
51 5.2.2 Durability of markings
5.3 Information for selection
5.3.1 General
5.3.2 General information
52 5.3.3 Information related to meters / metering elements
5.3.4 Information related to stand-alone tariff-and load control equipment
5.3.5 Information related to supply control and load control switches
5.4 Information for installation and commissioning
5.4.1 General
53 5.4.2 Handling and mounting
5.4.3 Enclosure
5.4.4 Connection
55 5.4.5 Protection
56 5.4.6 Auxiliary power supply
5.4.7 Supply for external devices
5.4.8 Batteries
5.4.9 Self-consumption
57 5.4.10 Commissioning
5.5 Information for use
5.5.1 General
5.5.2 Display, push buttons and other controls
5.5.3 Switches
58 5.5.4 Connection to user’s equipment
5.5.5 External protection devices
5.5.6 Cleaning
5.6 Information for maintenance
6 Protection against electrical shock
6.1 General requirements
59 6.2 Determination of accessible parts
6.2.1 General
6.2.2 Examination
60 6.2.3 Openings above parts that are hazardous live
6.2.4 Openings for pre-set controls
Figures
Figure 1 – Measurements through openings in enclosures
61 6.2.5 Wiring terminals
6.3 Limit values for accessible parts
6.3.1 General
6.3.2 Levels in normal condition
6.3.3 Levels in single fault condition
62 Figure 2 – Maximum duration of short-term accessible voltages in single fault condition (see 6.3.3 a))
63 Figure 3 – Capacitance level versus voltage in normal condition and single fault condition (see 6.3.2 c) and 6.3.3 c))
64 6.4 Primary means of protection (protection against direct contact)
6.4.1 General
6.4.2 Equipment case
6.4.3 Basic insulation
6.4.4 Impedance
65 6.5 Additional means of protection in case of single fault conditions (protection against indirect contact)
6.5.1 General
6.5.2 Protective bonding
Figure 4 – Acceptable arrangements of protection means against electric shock
67 Figure 5 – Examples of binding screw assemblies
68 Table 4 – Tightening torque for binding screw assemblies
69 6.5.3 Supplementary insulation and reinforced insulation
6.5.4 Protective impedance
6.5.5 Automatic disconnection of the supply
70 6.5.6 Current- or voltage-limiting device
6.6 Connection to external circuits
6.6.1 General
71 6.6.2 Terminals for external circuits
6.6.3 Terminals for stranded conductors
6.7 Insulation requirements
6.7.1 General – Electrical stresses, overvoltages and overvoltage categories
72 6.7.2 The nature of insulation
Table 5 – Multiplication factors for clearance for altitudes up to 5 000 m
75 Table 6 – Overview of clauses specifying requirements and tests for insulations
76 6.7.3 Insulation requirements for mains-circuits
Table 7 – Nominal / rated voltages and rated impulse voltages
77 Table 8 – Clearances for mains-circuits
78 Table 9 – Creepage distances for mains-circuits
79 Table 10 – Test voltages for solid insulation in mains-circuits
Table 11 – Test voltages for testing long-term stress of solid insulation in mains-circuits
80 Figure 6 – Distance between conductors on an interface between two layers
Figure 7 – Distance between adjacent conductors along an interface of an inner layer
81 Table 12 – Minimum values for distance or thickness of solid insulation
82 6.7.4 Insulation requirements for non-mains-circuits
Figure 8 – Distance between adjacent conductors located between the same two layers
83 Table 13 – Clearances and test voltages for non-mains-circuits derived from mains-circuits of overvoltage category III
Table 14 – Creepage distances for non-mains-circuits
85 Table 15 – Minimum values for distance or thickness (see 6.7.4.4.2 to 6.7.4.4.4)
86 6.7.5 Insulation in circuits not addressed in 0 or 6.7.4
88 Table 16 – Clearance values for the calculation of 6.7.5.2
89 Table 17 – Test voltages based on clearances
90 Figure 9 – Example of recurring peak voltage
91 Table 18 – Clearances for basic insulation in circuits having recurring peak voltages
92 6.7.6 Reduction of transient overvoltages by the use of overvoltage limiting devices
6.8 Insulation requirements between circuits and parts
93 Table 19 – Isolation classes for non-mains-circuits
94 Table 20 – Insulation requirements between any two circuits
96 6.9 Constructional requirements for protection against electric shock
6.9.1 General
6.9.2 Insulating materials
6.9.3 Colour coding
6.9.4 Equipment case
97 6.9.5 Terminal blocks
6.9.6 Insulating materials of supply control and load switches
98 6.9.7 Terminals
100 6.9.8 Requirements for current circuits
103 Table 21 – Summary of requirements for current circuits of direct connected meters without SCS
104 Table 22 – Summary of requirements for current circuits of direct connected meters with SCS
106 Table 23 – Summary of requirements for load control switches
107 6.10 Safety related electrical tests
6.10.1 Overview
108 Figure 10 – Flowchart of safety related electrical tests
109 6.10.2 Test methods
112 6.10.3 Testing of voltage circuits
Table 24 – Correction factors according to test site altitude for test voltages for clearances
114 6.10.4 Dielectric tests
117 Table 25 – AC voltage test
120 6.10.5 Electrical tests on current circuits of direct connected meters without supply control switches (SCSs)
121 6.10.6 Electrical tests on current circuits of direct connected meters with SCSs
Table 26 – Test sequence and sample plan for supply control switches
124 Table 27 – Power factor ranges of the test circuit
127 6.10.7 Electrical tests on load control switches (LCSs)
128 Table 28 – Test sequence and sample plan for load control switches
130 7 Protection against mechanical hazards
7.1 General
7.2 Sharp edges
131 7.3 Provisions for lifting and carrying
8 Resistance to mechanical stresses
8.1 General
8.2 Spring hammer test
132 9 Protection against spread of fire
9.1 General
133 9.2 Eliminating or reducing the sources of ignition within the equipment
9.3 Containment of fire within the equipment, should it occur
9.3.1 General
Figure 11 – Flow chart to explain the requirements for protection against the spread of fire
134 9.3.2 Constructional requirements
9.4 Limited-energy circuit
135 Table 29 – Limits of maximum available current
Table 30 – Values for overcurrent protection devices
136 9.5 Overcurrent protection
10 Equipment temperature limits and resistance to heat
10.1 Surface temperature limits for protection against burns
137 10.2 Temperature limits for terminals
Table 31 – Surface temperature limits in normal condition
138 10.3 Temperatures of internal parts
Table 32 – Temperature limits for terminals
139 Table 33 – Maximum measured total temperatures for internal materials and components
140 10.4 Temperature test
141 10.5 Resistance to heat
10.5.1 Non-metallic enclosures
142 10.5.2 Insulating materials
11 Protection against penetration of dust and water
Figure 12 – Ball-pressure test apparatus
144 12 Protection against liberated gases and substances explosion and implosion – Batteries and battery charging
13 Components and sub-assemblies
13.1 General
145 Figure 13 – Flow chart for conformity options 13.1 a), b), c) and d)
146 13.2 Mains transformers tested outside equipment
13.3 Printed wiring boards
13.4 Components bridging insulation
13.5 Circuits or components used as transient overvoltage limiting devices
14 Hazards resulting from application – Reasonably foreseeable misuse
147 15 Risk assessment
148 Annexes
Annex A (normative) Measuring circuits for touch current
A.1 Measuring circuit for a.c. with frequencies up to 1 MHz and for d.c.
Figure A.1 – Measuring circuit for a.c. with frequencies up to 1 MHz and for d.c.
149 A.2 Measuring circuits for sinusoidal a.c. with frequencies up to 100 Hz and for d.c.
A.3 Current measuring circuit for electrical burns at high frequencies
Figure A.2 – Measuring circuits for sinusoidal a.c. with frequencies up to 100 Hz and for d.c.
150 A.4 Current measuring circuit for wet location
Figure A.3 – Current measuring circuit for electrical burns
Figure A.4 – Current measuring circuit for wet contact
151 Annex B (informative) Examples for insulation between parts
B.1 Insulation between parts – Example 1
Figure B.1 – Insulation between parts – Example 1
152 B.2 Insulation between parts – Example 2
Figure B.2 – Insulation between parts – Example 2
153 B.3 Insulation between parts – Example 3
Figure B.3 – Insulation between parts – Example 3
154 B.4 Insulation between parts – Example 4
Figure B.4 – Insulation between parts – Example 4
155 B.5 Insulation between parts – Example 5
Figure B.5 – Insulation between parts – Example 5
157 Annex C (informative) Examples for direct connected meters equipped with supply control and load control switches
Figure C.1 – Single phase two wire meter with UC2 SCS and 25A LCS
158 Figure C.2 – Three phase four wire meter with UC2 SCS and 2A auxiliary control switch
159 Annex D (normative) Test circuit diagram for the test of long term overvoltage withstand
Figure D.1 – Circuit for three-phase four-wire meters to simulate long term overvoltage, voltage moved to L3
Figure D.2 – Voltages at the meter under test
160 Annex E (normative) Test circuit diagram for short current test on the current circuit of direct connected meters
Figure E.1 – Test circuit for verification of short-time withstand currenttest on current circuits with and without supply control switches
161 Figure E.2 – Example of short-circuit carrying test record in the case of a single-pole equipment on single-phase a.c.
162 Annex F (informative) Examples for voltage tests
Figure F.1 – Test arrangement for voltage tests: 3 phase 4 wire direct connected meter with supply control and load control switches
164 Figure F.2 – Test arrangement for voltage tests: 3 phase 4 wire transformer connected meter
166 Annex G (normative) Additional a.c. voltage tests for electromechanical meters
Table G.1 – AC voltage tests of electromechanical meters
167 Annex H (normative) Test equipment for cable flexion and pull test
Figure H.1 – Test equipment for cable flexion and pull test (see 6.9.7.3)
168 Table H.1 – Test values for flexion and pull-out tests for round copper conductors
169 Annex I (informative) Routine tests
I.1 General
I.2 Protective earth
I.3 AC power-frequency high-voltage test for mains-circuits
I.4 Mains-circuits with voltage limiting devices
170 Annex J (informative) Examples of battery protection
Figure J.1 – Non-rechargeable battery protection
Figure J.2 – Rechargeable battery protection
171 Annex K (informative) Rationale for specifying overvoltage category III
K.1 Transient overvoltage requirements in TC 13 standards
K.2 Electricity meters mentioned in basic safety publications and group safety publications
K.2.1 IEC 60664-1
172 K.2.2 IEC 60364-4-44
K.2.3 IEC 61010-1
173 K.3 Conclusion
174 Annex L (informative) Overview of safety aspects covered
Table L.1 – Overview of safety aspects
189 Annex M (informative) Index of defined terms
192 Bibliography
BS EN 62052-31:2016
$256.21