BS EN IEC 62271-100:2021
$215.11
High-voltage switchgear and controlgear – Alternating current circuit-breakers
Published By | Publication Date | Number of Pages |
BSI | 2021 | 302 |
IEC 62271-100:2021 is applicable to three-phase AC circuit-breakers designed for indoor or outdoor installation and for operation at frequencies of 50 Hz and/or 60 Hz on systems having voltages above 1 000 V. This document includes only direct testing methods for making-breaking tests. For synthetic testing methods refer to IEC 62271-101. This third edition cancels and replaces the second edition published in 2008, Amendment 1:2012 and Amendment 2:2017. This edition constitutes a technical revision. The main changes with respect to the previous edition are listed below: ā the document has been updated to IEC 62271-1:2017; ā Amendments 1 and 2 have been included; ā the definitions have been updated, terms not used have been removed; ā Subclauses 7.102 through 7.108 have been restructured.
PDF Catalog
PDF Pages | PDF Title |
---|---|
2 | undefined |
5 | Annex ZA (normative)Normative references to international publicationswith their corresponding European publications |
7 | English CONTENTS |
16 | FOREWORD |
18 | 1 Scope 2 Normative references |
19 | 3 Terms and definitions |
20 | 3.1 General terms and definitions |
24 | 3.2 Assemblies 3.3 Parts of assemblies 3.4 Switching devices |
26 | 3.5 Parts of circuit-breakers |
30 | 3.6 Operational characteristics |
32 | 3.7 Characteristic quantities |
34 | Figures Figure 1 ā Typical oscillogram of a three-phase short-circuit make-break cycle |
35 | Figure 2 ā Circuit-breaker without switching resistors ā Opening and closing operations |
36 | Figure 3 ā Circuit breaker without switching resistors ā Close-open cycle |
37 | Figure 4 ā Circuit-breaker without switching resistors ā Reclosing (auto-reclosing) |
38 | Figure 5 ā Circuit-breaker with switching resistors ā Opening and closing operations |
39 | Figure 6 ā Circuit-breaker with switching resistors ā Close-open cycle |
40 | Figure 7 ā Circuit-breaker with switching resistors ā Reclosing (auto-reclosing) |
48 | 3.8 Index of definitions |
52 | 4 Normal and special service conditions 5 Ratings 5.1 General |
53 | 5.2 Rated voltage (Ur) 5.3 Rated insulation level (Ud, Up, Us) 5.4 Rated frequency (fr) 5.5 Rated continuous current (Ir) 5.6 Rated short-time withstand current (Ik) 5.7 Rated peak withstand current (Ip) 5.8 Rated duration of short-circuit (tk) 5.9 Rated supply voltage of auxiliary and control circuits (Ua) 5.10 Rated supply frequency of auxiliary and control circuits 5.11 Rated pressure of compressed gas supply for controlled pressure systems |
54 | 5.101 Rated short-circuit breaking current (Isc) |
55 | Figure 8 ā Determination of short-circuit making and breaking currents,and of percentage DC component |
56 | Figure 9 ā Percentage DC component in relation to the time interval fromthe initiation of the short-circuit for the different time constants |
57 | 5.102 Rated first-pole-to-clear factor (kpp) 5.103 Rated short-circuit making current 5.104 Rated operating sequence 5.105 Rated out-of-phase making and breaking current |
58 | 5.106 Rated capacitive currents |
59 | Tables Table 1 ā Preferred values of rated capacitive currents |
60 | 6 Design and construction 6.1 Requirements for liquids 6.2 Requirements for gases 6.3 Earthing |
61 | 6.4 Auxiliary and control equipment and circuits 6.5 Dependent power operation 6.6 Stored energy operation 6.7 Independent unlatched operation (independent manual or power operation) 6.8 Manually operated actuators 6.9 Operation of releases |
62 | 6.10 Pressure/level indication 6.10.1 Gas pressure |
63 | 6.10.2 Liquid level 6.11 Nameplates |
64 | Table 2 ā Nameplate information |
65 | 6.12 Locking devices 6.13 Position indication 6.14 Degrees of protection provided by enclosures 6.15 Creepage distances for outdoor insulators 6.16 Gas and vacuum tightness 6.17 Tightness for liquid systems 6.18 Fire hazard (flammability) 6.19 Electromagnetic compatibility (EMC) 6.20 X-ray emission 6.21 Corrosion |
66 | 6.22 Filling levels for insulation, switching and/or operation 6.101 Requirements for simultaneity of poles during single closing and single opening operations 6.102 General requirement for operation 6.103 Pressure limits of fluids for operation |
67 | 6.104 Vent outlets 6.105 Time quantities 6.106 Mechanical loads |
68 | 6.107 Circuit-breaker classification Table 3 ā Examples of static horizontal and vertical forces for static terminal load |
69 | Table 4 ā Number of mechanical operations |
70 | 7 Type tests 7.1 General 7.1.1 Basics |
71 | 7.1.2 Information for identification of test objects 7.1.3 Information to be included in type-test reports Table 5 ā Type tests |
72 | 7.2 Dielectric tests 7.2.1 General Table 6 ā Invalid tests |
73 | 7.2.2 Ambient air conditions during tests 7.2.3 Wet test procedure 7.2.4 Arrangement of the equipment 7.2.5 Criteria to pass the test 7.2.6 Application of test voltage and test conditions 7.2.7 Tests of switchgear and controlgear of Ur ā¤ 245 kV 7.2.8 Tests of switchgear and controlgear of Ur > 245 kV |
74 | 7.2.9 Artificial pollution tests for outdoor insulators |
75 | 7.2.10 Partial discharge tests 7.2.11 Dielectric tests on auxiliary and control circuits 7.2.12 Voltage test as a condition check Table 7 ā Test requirements for voltage tests as condition checkfor metal-enclosed circuit-breakers |
77 | 7.3 Radio interference voltage (RIV) test 7.4 Resistance measurement |
78 | 7.5 Continuous current tests 7.5.1 Condition of the test object 7.5.2 Arrangement of the equipment 7.5.3 Test current and duration 7.5.4 Temperature measurement during the test 7.5.5 Resistance of the main circuit 7.5.6 Criteria to pass the test |
79 | 7.6 Short-time withstand current and peak withstand current tests 7.6.1 General 7.6.2 Arrangement of the equipment and of the test circuit 7.6.3 Test current and duration 7.6.4 Conditions of the test object after test 7.7 Verification of the protection 7.7.1 Verification of the IP coding 7.7.2 Verification of the IK coding 7.8 Tightness tests 7.9 Electromagnetic compatibility tests (EMC) |
80 | 7.10 Additional tests on auxiliary and control circuits 7.10.1 General 7.10.2 Functional tests 7.10.3 Verification of the operational characteristics of the auxiliary contacts 7.10.4 Environmental tests 7.10.5 Dielectric test 7.11 X-radiation test procedure for vacuum interrupters 7.101 Mechanical and environmental tests |
84 | Table 8 ā Number of operating sequences |
87 | Figure 10 ā Example of wind velocity measurement |
89 | Figure 11 ā Test sequence for low temperature test |
90 | Figure 12 ā Test sequence for high temperature test |
92 | Figure 13 ā Humidity test |
93 | 7.102 Miscellaneous provisions for making and breaking tests |
96 | Figure 14 ā Example of reference mechanical characteristics (idealised curve) |
97 | Figure 15 ā Reference mechanical characteristics of Figure 14with the envelopes centred over the reference curve (+5 %, ā5 %) |
98 | Figure 16 ā Reference mechanical characteristics of Figure 14with the envelope fully displaced upward from the reference curve (+10 %, ā0 %) Figure 17 ā Reference mechanical characteristics of Figure 14with the envelope fully displaced downward from the reference curve (+0 %, ā10 %) |
100 | Figure 18 ā Equivalent testing set-up for unit testing of circuit-breakerswith more than one separate making and breaking units |
101 | Figure 19 ā Earthing of test circuits for single-phase short-circuit tests,kpp = 1,5 |
102 | Figure 20 ā Earthing of test circuits for single-phase short-circuit tests,kpp = 1,3 Figure 21 ā Test circuit for single-phase out-of-phase tests |
103 | Figure 22 ā Test circuit for out-of-phase tests using two voltagesseparated by 120 electrical degrees Figure 23 ā Test circuit for out-of-phase tests with one terminal of the circuit-breaker earthed (subject to agreement of the manufacturer) |
104 | Figure 24 ā Example of prospective test TRV with four-parameter envelopewhich satisfies the conditions to be met during type test āCase of specified TRV with four-parameter reference line |
105 | Figure 25 ā Example of prospective test TRV with two-parameter envelopewhich satisfies the conditions to be met during type test:case of specified TRV with two-parameter reference line |
106 | Figure 26 ā Example of prospective test TRV-waves andtheir combined envelope in two-part test |
111 | 7.103 General considerations for making and breaking tests |
113 | Figure 27 ā Earthing of test circuits for three-phase short-circuit tests, kpp = 1,5 |
114 | Figure 28 ā Earthing of test circuits for three-phase short-circuit tests, kpp = 1,3 |
116 | Figure 29 ā Determination of power frequency recovery voltage |
117 | Table 9 ā Standard values of ITRV ā Rated voltages 100 kV and above |
118 | 7.104 Demonstration of arcing times |
119 | Figure 30 ā Graphical representation of the time parameters for the demonstrationof arcing times in three-phase tests of test-duty T100a |
120 | Figure 31 ā Graphical representation of an example of the three validsymmetrical breaking operations for kpp = 1,5 |
121 | Figure 32 ā Graphical representation of the three valid symmetrical breakingoperations for kpp = 1,2 or 1,3 |
122 | Table 10 ā Last current loop parameters in three-phase testsand in single-phase tests in substitution for three-phase conditionsin relation with short-circuit test-duty T100a ā Tests for 50 Hz operation |
123 | Table 11 ā Last current loop parameters in three-phase testsand in single-phase tests in substitution for three-phase conditionsin relation with short-circuit test-duty T100a ā Tests for 60 Hz operation |
125 | Figure 33 ā Graphical representation of an example of the three valid asymmetrical breaking operations for kpp = 1,5 |
126 | Figure 34 ā Graphical representation of an example of the three valid asymmetrical breaking operations for kpp = 1,2 or 1,3 |
127 | Table 12 ā Prospective TRV parameters for single-phase tests in substitution for three-phase tests to demonstrate the breaking of the second-pole-to-clear for kpp = 1,3 |
128 | Table 13 ā Prospective TRV parameters for single-phase tests in substitution for three-phase tests to demonstrate the breaking of the third-pole-to-clear for kpp = 1,3 |
130 | Figure 35 ā Example of a graphical representation of the three valid symmetrical breaking operations for single-phase tests in substitution of three-phase conditionsfor kpp = 1,5 |
131 | Figure 36 ā Example of a graphical representation of an example of the three valid symmetrical breaking operations for single-phase tests in substitution of three-phase conditions for kpp = 1,2 or 1,3 |
133 | Figure 37 ā Example of a graphical representation of an example of the three valid asymmetrical breaking operations for single-phase tests in substitution of three-phase conditions for kpp = 1,5 |
134 | Figure 38 ā Example of a graphical representation of an example of the three valid asymmetrical breaking operations for single-phase tests in substitution of three-phasefor kpp = 1,2 and 1,3 |
135 | Table 14 ā Standard multipliers for TRV values for second and third clearing poles Table 15 ā Arcing window for tests with symmetrical current |
136 | Figure 39 ā Graphical representation of the arcing window andthe pole factor kp, determining the TRV of the individual pole,for systems with a kpp of 1,2 Figure 40 ā Graphical representation of the arcing window and the pole factor kp, determining the TRV of the individual pole, for systems with a kpp of 1,3 |
137 | 7.105 Short-circuit test quantities Figure 41 ā Graphical representation of the arcing window and the pole factor kp, determining the TRV of the individual pole, for systems with a kpp of 1,5 |
140 | Figure 42 ā Representation of a specified TRV by a 4-parameterreference line and a delay line |
141 | Figure 43 ā Representation of a specified TRV by a two-parameterreference line and a delay line Figure 44 ā Basic circuit for terminal fault with ITRV |
142 | Figure 45 ā Representation of ITRV in relationship to TRV |
143 | Table 16 ā Values of prospective TRV for class S1 circuit-breakers rated for kpp = 1,5 |
145 | Table 17 ā Values of prospective TRV for class S1 circuit-breakers rated for kpp = 1,3 |
147 | Table 18 ā Values of prospective TRV for class S2 circuit-breakers rated for kpp = 1,5 |
149 | Table 19 ā Values of prospective TRV for class S2 circuit-breakers rated for kpp = 1,3 |
152 | Table 20 ā Values of prospective TRV for circuit-breakers rated for kpp = 1,2 or 1,3 ā Rated voltages of 100 kV and above |
154 | Table 21 ā Values of prospective TRV for circuit-breakers rated for kpp = 1,5 āRated voltages of 100 kV to 170 kV |
156 | Figure 46 ā Example of line transient voltage with time delay with non-linear rate of rise |
157 | Table 22 ā Values of prospective TRV for out-of-phase testson class S1 circuit-breakers for kpp = 2,5 |
158 | Table 23 ā Values of prospective TRV for out-of-phase testson class S1 circuit-breakers for kpp = 2,0 Table 24 ā Values of prospective TRV for out-of-phase testson class S2 circuit-breakers for kpp = 2,5 |
159 | Table 25 ā Values of prospective TRV for out-of-phase tests onclass S2 circuit-breakers for kpp = 2,0 Table 26 ā Values of prospective TRV for out-of-phase tests on circuit-breakersrated for kpp = 2,5 ā Rated voltages of 100 kV to 170 kV |
160 | 7.106 Short-circuit test procedure Table 27 ā Values of prospective TRV for out-of-phase tests on circuit-breakersrated for kpp = 2,0 ā Rated voltages of 100 kV and above |
162 | 7.107 Terminal fault tests |
166 | 7.108 Additional short-circuit tests |
167 | Figure 47 ā Necessity of additional single-phase tests and requirements for testing |
168 | Table 28 ā Prospective TRV parameters for single-phase and double-earth fault tests |
169 | 7.109 Short-line fault tests |
170 | Table 29 ā Values of line characteristics for short-line faults |
171 | Figure 48 ā Basic circuit arrangement for short-line fault testing and prospective TRV-circuit-type a) according to 7.109.3: Source side and line side with time delay |
172 | Figure 49 ā Basic circuit arrangement for short-line fault testing ā circuit type b1)according to 7.109.3: Source side with ITRV and line side with time delay |
173 | Figure 50 ā Basic circuit arrangement for short-line fault testing ā circuit type b2)according to 7.109.3: Source side with time delay and line side without time delay |
174 | Figure 51 ā Example of a line side transient voltage with time delay |
175 | Figure 52 ā Flow chart for the choice of short-line fault test circuits |
177 | Figure 53 ā Compensation of deficiency of the source side time delayby an increase of the excursion of the line side voltage |
179 | Table 30 ā Values of prospective TRV for the supply circuit of short-line fault tests |
180 | 7.110 Out-of-phase making and breaking tests |
181 | Table 31 ā Test-duties to demonstrate the out-of-phase rating |
182 | 7.111 Capacitive current tests |
184 | Table 32 ā Specified values of u1, t1, uc and t2 |
186 | Table 33 ā Common requirements for test-duties |
193 | Figure 54 ā Recovery voltage for capacitive current breaking tests |
195 | Figure 55 ā Reclassification procedure for line and cable-charging current tests |
196 | 7.112 Requirements for making and breaking tests on class E2 circuit-breakers having a rated voltage above 1 kV up to and including 52 kV Figure 56 ā Reclassification procedure for capacitor bank current tests |
197 | 8 Routine tests 8.1 General Table 34 ā Operating sequence for electrical endurance test on class E2circuit-breakers for auto-reclosing duty |
198 | 8.2 Dielectric test on the main circuit Table 35 ā Application of voltage for dielectric test on the main circuit |
199 | Table 36 ā Test voltage for partial discharge test |
200 | 8.3 Tests on auxiliary and control circuits 8.4 Measurement of the resistance of the main circuit 8.5 Tightness test 8.6 Design and visual checks 8.101 Mechanical operating tests |
202 | 9 Guide to the selection of switchgear and controlgear (informative) 9.101 General |
204 | 9.102 Selection of rated values for service conditions |
206 | 9.103 Selection of rated values for fault conditions |
210 | 9.104 Selection for electrical endurance in networks of rated voltage above 1 kV and up to and including 52 kV 9.105 Selection for switching of capacitive loads 10 Information to be given with enquiries, tenders and orders (informative) 10.1 General 10.2 Information with enquiries and orders |
211 | 10.3 Information to be given with tenders |
213 | 11 Transport, storage, installation, operation instructions and maintenance 11.1 General 11.2 Conditions during transport, storage and installation 11.3 Installation |
219 | 11.4 Operating instructions 11.5 Maintenance |
220 | 11.101 Resistors and capacitors 12 Safety 13 Influence of the product on the environment |
221 | Annexes Annex A (normative)Calculation of TRVs for short-line faultsfrom rated characteristics A.1 Basic approach |
223 | Figure A.1 ā Typical graph of line and source side TRV parameters āLine side and source side with time delay Table A.1 ā Ratios of voltage-drop and source-side TRV |
224 | A.2 Transient voltage on line side A.3 Transient voltage on source side A.3.1 Rated voltages of 100 kV and above |
226 | Figure A.2 ā Actual course of the source side TRVfor short-line fault L90, L75 and L60 |
227 | Figure A.3 ā Typical graph of line and source side TRV parameters āLine side and source side with time delay, source side with ITRV |
228 | A.3.2 Rated voltages equal and higher than 15 kV and below 100 kV A.4 Examples of calculations A.4.1 General |
229 | A.4.2 Test circuit with source side and line side with time delay (L90 and L75 for 245 kV, 50 kA, 50 Hz) |
230 | A.4.3 Circuit with source side with ITRV, line side with time delay (L90 for 245 kV, 50 kA, 50 Hz) |
231 | Annex B (normative)Tolerances on test quantities during type tests |
232 | Table B.1 ā Tolerances on test quantities for type tests |
240 | Annex C (normative)Records and reports of type tests C.1 Information and results to be recorded C.2 Information to be included in type test reports C.2.1 General C.2.2 Apparatus tested C.2.3 Rated characteristics of circuit-breaker, including its operating devices and auxiliary equipment |
241 | C.2.4 Test conditions (for each series of tests) C.2.5 Short-circuit making and breaking tests C.2.6 Short-time withstand current test |
242 | C.2.7 No-load operation C.2.8 Out-of-phase making and breaking tests C.2.9 Capacitive current tests |
243 | C.2.10 Oscillographic and other records |
244 | Annex D (normative)Method of determination of the prospective TRV D.1 General D.2 Drawing the envelope |
245 | D.3 Determination of parameters |
246 | Figure D.1 ā Representation by four parameters of a prospective TRV of a circuit āCase D.2 c) 1) Figure D.2 ā Representation by four parameters of a prospective TRV of a circuit āCase D.2 c) 2) |
247 | Figure D.3 ā Representation by four parameters of a prospective TRV of a circuit āCase D.2 c) 3) i) Figure D.4 ā Representation by two parameters of a prospective TRV of a circuit āCase D.2 c) 3) ii) |
248 | Annex E (normative)Methods of determining prospective TRV waves E.1 General |
249 | Figure E.1 ā Effect of depression on the peak value of the TRV |
250 | E.2 General summary of the recommended methods |
251 | E.3 Detailed consideration of the recommended methods E.3.1 Group 1 ā Direct short-circuit breaking Figure E.2 ā Breaking with arc-voltage present |
252 | Figure E.3 ā TRV in case of ideal breaking Figure E.4 ā Breaking with pronounced premature current-zero |
253 | Figure E.5 ā Relationship between the values of current and TRV occurring in testand those prospective to the system |
254 | E.3.2 Group 2 ā Power-frequency current injection Figure E.6 ā Breaking with post-arc current |
255 | Figure E.7 ā Schematic diagram of power-frequency current injection apparatus |
256 | Figure E.8 ā Sequence of operation of power-frequency current injection apparatus |
257 | E.3.3 Group 3 ā Capacitor current injection |
258 | Figure E.9 ā Schematic diagram of capacitance injection apparatus |
259 | E.3.4 Groups 2 and 3 ā Methods of calibration Figure E.10 ā Sequence of operation of capacitor-injection apparatus |
261 | E.3.5 Group 4 ā Model networks E.3.6 Group 5 ā Calculation from circuit parameters E.3.7 Group 6 ā No-load switching of test circuits including transformers |
262 | E.3.8 Group 7 ā Combination of different methods E.4 Comparison of methods |
263 | Table E.1 ā Methods for determination of prospective TRV |
266 | Annex F (informative)Requirements for breaking of transformer-limited faults bycircuit-breakers with rated voltage higher than 1 kV F.1 General Figure F.1 ā First example of transformer-limited fault(also called transformer-fed fault) |
267 | F.2 Circuit-breakers with rated voltage less than 100 kV Figure F.2 ā Second example of transformer-limited fault(also called transformer-secondary fault) |
268 | Table F.1 ā Required values of prospective TRV for T30, for circuit-breakers intended to be connected to a transformer with a connection of small capacitance ā Rated voltage higher than 1 kV and less than 100 kV for non-effectively earthed neutral systems |
269 | F.3 Circuit-breakers with rated voltage from 100 kV to 800 kV F.4 Circuit-breakers with rated voltage higher than 800 kV Table F.2 ā Required values of prospective TRV for circuit-breakers with rated voltages higher than 800 kV intended to be connected to a transformer with a connection of low capacitance |
270 | Annex G (normative)Use of mechanical characteristics and related requirements |
271 | Annex H (normative)Requirements for making and breaking test proceduresfor metal-enclosed and dead tank circuit-breakers H.1 General H.2 Reduced number of making and breaking units for testing purposes |
272 | H.3 Tests for single pole in one enclosure H.3.1 General H.3.2 Terminal fault tests H.3.3 Capacitive current tests |
273 | Figure H.1 ā Test configuration considered in Table H.1, Table H.2 and Table H.3 Table H.1 ā Three-phase capacitive current breaking in service conditions:voltages on the source-side, load-side, and recovery voltages |
274 | Table H.2 ā Corresponding capacitive current-breaking tests in accordancewith 7.111.7 for single-phase laboratory tests. Values of voltageson the source-side, load-side, and recovery voltages |
275 | H.4 Tests for three poles in one enclosure H.4.1 Terminal fault tests H.4.2 Capacitive current tests |
276 | Table H.3 ā Capacitive current breaking in actual service conditions:maximum typical voltage values |
277 | Annex I (normative)Requirements for circuit-breakers with opening resistors I.1 General I.2 Switching performance to be verified I.2.1 General Figure I.1 ā Typical system configuration for breakingby a circuit-breaker with opening resistors |
278 | I.2.2 Tests of the making and breaking unit |
279 | Figure I.2 ā Test circuit for test-duties T60 and T100 |
280 | Figure I.3 ā Test circuit for test-duties T10, T30 and OP2 |
281 | Table I.1 ā Results of the TRV calculation for terminal faults and out-of-phase |
282 | Figure I.4 ā Example of an underdamped TRV for T100s(b),Ur = 1 100 kV Isc = 50 kA, fr = 50 Hz |
283 | Figure I.5 ā Example of an overdamped TRV for T10,Ur = 1 100 kV Isc = 50 kA, fr = 50 Hz |
284 | Figure I.6 ā Example of a test circuit for short-line fault test-duty L90 |
285 | Figure I.7 ā Example of real line simulation for short-line fault test-duty L90based on Ur = 1 100 kV, Isc = 50 kA and fr = 50 Hz Table I.2 ā Results of the TRV calculation for test-duty L90 |
287 | I.2.3 Tests on the resistor switch Figure I.8 ā Typical recovery voltage waveshape of capacitive current breakingon a circuit-breaker equipped with opening resistors |
288 | Figure I.9 ā Typical recovery voltage waveshape of T10(based on Ur = 1 100 kV, Isc = 50 kA and fr = 50 Hz) on the resistorswitch of a circuit-breaker equipped with opening resistors Table I.3 ā Results of the TRV calculations for test-duty T10 |
289 | I.2.4 Tests of the resistor stack |
290 | I.3 Insertion time of the resistor I.4 Current carrying performance I.5 Dielectric performance I.6 Mechanical performance I.7 Requirements for the specification of opening resistors I.8 Examples of recovery voltage waveshapes I.8.1 General |
291 | I.8.2 Terminal faults Figure I.10 ā TRV waveshapes for high short-circuit current breaking operation |
292 | Figure I.11 ā Currents in case of high short-circuit current breaking operation |
293 | Figure I.12 ā TRV shapes for low short-circuit current breaking operation |
294 | I.8.3 Line-charging current breaking Figure I.13 ā Currents in case of low short-circuit current breaking operation |
295 | Figure I.14 ā Voltage waveshapes for line-charging current breaking operation |
296 | Figure I.15 ā Current waveshapes for line-charging current breaking operation |
297 | Annex J (normative)Verification of capacitive current breakingin presence of single or two-phase earth faults J.1 General J.2 Test voltage J.3 Test current |
298 | J.4 Test-duty J.5 Criteria to pass the tests |
299 | Bibliography |